Dell PowerEdge R660 Installation and Service Manual

Removing the right control panel

Prerequisites

  1. Follow the safety guidelines listed in the Safety instructions.
  2. Follow the procedure listed in Before working inside your system.
  3. Remove the drive backplane cover.
  4. If installed, remove the air shroud.

Steps

  1. Disconnect the right control panel cable from the connector on the system board.
  2. Lift the latch, and slide the cable out of the clip.
    NOTE:Observe the routing of the cable as you remove the right control panel from the system.
  3. Using the Phillips #1 screwdriver, remove the screws that secure the right control panel to the system.
  4. Holding the cable, slide the right control panel out of the system.
    NOTE:The numbers on the image do not depict the exact steps. The numbers are for representation of sequence.
    Figure 1. Removing the right control panel
    This image shows how to remove the right control panel.